GLOBE VALVE  VSG,VMB16                  3 
65 to 150 mm 2-Way and 3-way Globe 
Valve Bodies: Cast Iron Flanged, PN 16 
Body Rating 
General
The VSG and VMB16 Series 2-way and  
3-way globe valves are engineered  
specifically for temperature control  
applications requiring an equal percentage 
flow characteristic and a high degree of  
control precision. Common applications  
include hot water, chilled water and low 
pressure steam coils and heat exchangers in 
air handling units, chillers, boilers and cool-
ing towers. 
 
The VSG and VMB16 Series valves are 
available with PN16 flanged connections in 
2-way and 3-way configurations. The  
service port A of all valves is fully closed to 
port AB with the stem up and fully open with 
the stem down (push-down-to-open) while 
the bypass port B to port AB of all 3-way 
valves is vice versa. 
 
All VSG and VMB16 Series valves are  
operated by SH Series (general purpose) or 
MVL Series (heavy duty) electric actuators 
which are ordered separately.  The  
actuators are designed specially for  
mounting directly to VSG and VMB16 Series 
valves without the need of time-consuming 
field calibration. However, when a SH  
actuator is used, its stroke setting must be 
set to correspond with the specified valve 
stroke. 
 
 
Material 
Body and Seat: 
     Cast Iron 
Stem:                      Stainless Steel 
Plug:                       Forged brass 
Packing:                 Viton O-ring with 
                               Teflon Scrapper ring 
 
 
 
Specification
  
Working Pressure:           16 bar 
Pipe Connection:             PN16 Flange 
Flow Characteristics:       ¡°A¡° equal percentage 
                                        ¡°B¡± Linear (by-pass) 
Leakage:                          0.03% of Kv ¡°A¡±,  2% of Kv ¡°B¡± 
Fluid Limitations :            -10¡­150
o
C Water (max. 50% Glycol) 
                                        Max. 150
o
C at 2.5 bar (Steam)             
                               
The specification above are normal and conform to generally  
acceptable industry standard.  Cyrus is not responsible for  