General 
The RT900 Series room thermostats provide  
on/off control, consistent performance and  
contemporary styling.  This series controls a 
variety of two-pipe and four-pipe fan coil  
systems as well as other heating and cooling 
applications. 
 
RT900 is an electro-mechanical thermostat for 
room mounting.  The sensing element is a  
quality bi-metal which reacts to change in  
temperature by creating a movement as a 
switching function.  The thermostat can also 
control the fan speed with three position  
continuously or automatically with the  
temperature switching action. 
 
Features 
.
Attractive contemporary styling 
.
High quality bi-metal sensor  provides       
constant and close 
.
temperature differential over the  whole       
temperature range  
.
System ˇ°OFFˇ± position breaks all circuits 
.
Simple on-site set-point re-calibration  
.
All slide switches for ease of operation  
.
Easy wire termination 
.
Optional set-point range limit stops       
available to conserve energy 
.
Customizing available 
 
Models
RT901 
System switch:       On/Off 
Fan Switch:            Hi-Med-Low 
RT902 
(Two-pipe) 
System Switch: 
     Heat/Off/Cool 
Fan Switch:            Hi-Med-Low
 
RT903
 (Four-pipe) 
System Switch: 
     Heat/Off/Cool 
Fan Switch:            Hi-Med-Low
Specification 
Operating Differential      Approximately  1K 
Range                              10ˇ­30 
o
Sensing Element             B-metal type 
Housing Materials            Self-extinguishing, molded ABS 
Electrical Rating               
thermostat                       6(1)A cooling, 6(1.5)A heating,  
switches                           6A resistive, 4A inductive 
Ambient Limitation           0ˇ­50 
o
C   
Wire connection              Screw-down connection, 
                                        wire size 1mm
2
 or 18AWG 
Agency Approval             CE  compliant 
Shipping weight               180g 
 
ROOM THERMOSTAT  RT900               2
 
For Low Voltage and Line Voltage  
Control of Valves, Relays and Fan Motors 
in Fan Coil or Heat Pump Units 
The specification above are normal and conform to generally  
acceptable industry standard.  Cyrus is not responsible for  