TECHNICAL DATA                                  5 
Zone Valve Engineering & Installation 
Reference Notes 
Locating & Mounting 
Electric valves, like all other mechanical  
equipment, should be installed with a degree of      
accessibility to enable quick and economical 
servicing or replacement.  On high rise  
buildings, use reducing valves on branch lines 
on lower floors. 
 
Note For Fan Coil Installations 
Valve motor and gear train will not function  
properly when wet.  Motor housing must be  
protected from drippage.  Motor housing need 
not be protected from condensation on its  
attached valve body when installation in  
horizontal piping, if valve is positioned within 85
o
 
of upright position,  (See Fig. 1).  When 
mounted in vertical piping, motor housing must 
be protected from drippage.  
 
Valves with Sweat Connections 
Prior to soldering, place valve in manually open 
position by moving lever to retaining notch.  
Ends of water supply tubing must be thoroughly 
clean for a minimum distance of 25 mm from 
end. 
 
Instructions for Sweating 
Use only lead or tin based solder with melting 
point below 300 
o
C.  Do not overheat valve body. 
 
CAUTION 
This valve is not intended for use with  systems 
that require frequent mark-up water.  Systems 
which are primarily for domestic hot water    
supply are sometimes also used for heating  
purposes.  In this type of application, the large 
volume of mark-up or fresh water will contain 
dissolved oxygen and minerals which can cause 
early valve failure. 
The specification above are normal and conform to generally  
acceptable industry standard.  Cyrus is not responsible for  
damages resulting from misapplication or misuse of its products. 
Normal Use 
All zone valves designed to provide a useful life of at least 
100,000 cycles.  A cycle being defined as operation of the 
zone valve to its normal stop and then allowing it to return 
its normal position. 
 
Manual Operating Lever 
When valves are placed in the open position with the  
manual lever, the paddle is removed from the seat or port.  
This must be done prior to soldering sweat valves.  Move 
the lever slowly to the open position and hold in the  
retaining notch until the gear is taken up by the  
return spring. 
 
THE MANUAL LEVER WILL RESET TO THE 
AUTOMATIC POSITION THE FIRST TIME  
THE VALVE IS CYCLED ELECTRICALLY. 
 
Figure 1       Mounting position