CONTROLLER  TC24                              1
 
Temperature Controller For Stand Alone 
Digital Control of Heat Pumps,  
Air-Handling Units and Terminal Units 
General 
The TC24 Series LCD microprocessor based 
controller provides combinations of on/off and 
3-wire floating (incremental) or 0-10 VDC con-
trol (P or PI).  Large LCD allows users to read 
and set the functions accurately.  This series 
controls a variety of two-pipe and  
four-pipe  air handling units, heat pumps,  
unitary equipment and various cooling and 
heating applications. 
 
The microprocessor combines a proportional 
plus integral (PI) control algorithm which   
provides precise and stable control under 
varying system capacity and load conditions.  
Most of the functions can be selected and be 
set by pressing buttons easily.  
  
Features 
?
Touch pad keys 
?
Large LCD  
?
On/off or 3-wire floating outputs (P or PI) 
?
0 ¨C 10 VDC outputs (P or PI) 
?
Adjustable P-band and I-time 
?
Adjustable dead-band 
?
Adjustable set-point limit 
?
Fahrenheit or Celsius display capability  
?
Manual or automatic changeover 
?
Remote and changeover sensor 
?
Output status indicator
 
?
Customizing availability 
 
?
Networking availability
 
 
Models 
3-wire floating models 
TC24T1       Single output (Auto changeover) 
TC24T2       Dual output (Four-pipe) 
 
0-10 VDC models
 
TC24A1       Single output (Auto changeover) 
TC24A2       Dual output (Four-pipe)
 
Specifications
 
Supply Voltage:
        
24 VAC +/- 15%, 50-60 Hz 
Outputs:
              
24 VAC, 20 VA (3-wire models) 
                                        0 ¨C 10 VDC (at least 1k ohm) 
Power Consumption:
    
24 VAC, 1 VA 
Sensing element:             NTC (10k ohm at 25 
o
C) 
Setpoint Deadband:
     
-1¡­+1K (factory setting) 
Setpoint Range:
 
      
0¡­30 
o
Ambient Limitations:
    
0¡­50 
o
C, 90% RH 
Agency Approval:            EMC and
 
CE compliant
 
Shipping Weight:   
     
120 g 
The specification above are normal and conform to generally  
acceptable industry standard.  Cyrus is not responsible for  
damages resulting from misapplication or misuse of its products. 